AT-GAS/C/H2 - Hydrogen Concentration Sensor

The AT‑GAS/C/H2 is a hydrogen concentration sensor designed for hazardous areas.

ATUT Gas Detection System – AT-GAS/C/H2 - Hydrogen Concentration Sensor

// DESCRIPTION

What it is

The sensor has two displays: one shows the communication parameters and is used during calibration, the other continuously displays the measured hydrogen concentration. The device is equipped with four dry contacts, a 4÷20 mA current output, a 5÷15 Hz frequency output and four 4‑state inputs. The built‑in battery allows operation without external power for at least 8 hours. The sensor can be connected to a gas monitoring system PLC via RS485 (Modbus RTU) or operate as a stand‑alone device.

The electrochemical measuring head provides high‑resolution measurement in the range of 0÷1000 ppm H2. Alarm states are signalled by a red LED and a buzzer (up to 97 dB). The sensor is additionally equipped with a temperature and humidity sensor.

// Features

What it does

01

Measurements

  • Hydrogen concentration measurement in the 0‑1000 ppm range
  • Accuracy: ±2% within the measuring range
  • Electrochemical measuring head
02

Design and Data Transmission

  • Intrinsically safe Ex ia design - Group I (M1) and Group II (2G)
  • IP54‑rated enclosure (IP65 available on request)
  • Operating range: -20 to +45 °C, humidity up to 95% (non‑condensing)
  • Outputs: 4 contacts, 4÷20 mA, 5÷15 Hz, RS485 (Modbus RTU); four 4‑state inputs
  • Built‑in battery - at least 8 h without external power
  • Alarm signalling: red LED and buzzer up to 97 dB
// Application

Where it works

01

  • Hazardous areas with explosive gas atmospheres
  • Safety and environmental monitoring systems
  • Industrial installations requiring continuous atmosphere monitoring
// Parameters

Technical data

ATEX certificate number
KDB 25ATEX0028
Power supply
Intrinsically safe power supply
Supply voltage
UN = 10÷15 VDC
Current consumption
<230 mA
Built-in battery
Intrinsically safe, capacity 2200 mAh
Type of measuring head
Electrochemical
Measurement method
Continuous
Measuring range
0÷1000 ppm H2
Accuracy
±2% (within the measuring range)
Alarm signalling: acoustic
Buzzer, up to 97 dB
Alarm signalling: optical
Red LED
Inputs
Four 4-state inputs
Outputs
Four dry contacts; Current output 4÷20 mA; Frequency output 5÷15 Hz; RS485 (Modbus RTU)
Explosion protection
I M1 Ex ia I Ma; II 2G Ex ia IIA T3 Gb
Working temperature range
−20÷45 °C
Working humidity range
0÷95% RH (non-condensing)
Casing protection degree
IP54 (IP65 available on request)
Dimensions (W × H × D)
~322 × 220.5 × 165 mm
Cable glands / connectors
6
Weight
4 kg
// Classification
Version
  • Iskrobezpieczeństwo (Ex i)
  • ATEX
  • Ex